PRESCRIPTIVE PROVISIONS FOR SEISMIC
STRENGTHENING OF CRIPPLE
WALLS AND SILL PLATE ANCHORAGE OF LIGHT, WOOD-FRAMED, RESIDENTIAL
BUILDINGS
SECTION A601 - GENERAL
A601.1 Purpose. The provisions of this chapter are
intended to promote
public safety and welfare by reducing the risk of earthquake induced
damage
to existing wood-framed residential buildings. The requirements
contained
in this chapter are prescriptive minimum standards intended to improve
the seismic performance of residential buildings, but will not
necessarily
prevent earthquake damage.
This chapter sets standards for strengthening that
may be approved by
the building official without requiring plans or calculations prepared
by an architect or an engineer. The provisions of this chapter are not
intended to prevent the use of any material or method of construction
not
prescribed herein. The building official may require that construction
documents for strengthening using alternate material or methods be
prepared
by an architect or engineer.
A601.2 Scope. The provisions of this chapter apply
to light, wood-frame
Group R, Division 3 and Group R, Division 1 Occupancies located in
Seismic
Zones 3 and 4, containing one or more of the structural weaknesses
specified
in Section A603.
EXCEPTION: The provisions of this chapter do not
apply to the buildings
or elements thereof, listed below. These buildings or elements require
analysis by an engineer or architect in accordance with Section A601.3
to determine appropriate strengthening.
1. Group R, Division 1 Occupancies with more than
four dwelling units.
2. Buildings with a lateral force-resisting system
using poles or columns
embedded in the ground.
3. Cripple walls that exceed 4 feet (1219 mm) in
height.
4. Buildings exceeding three stories in height and
any three-story building
with cripple wall studs exceeding 14 inches (356 mm) in height.
5. Buildings where the building official
determines that conditions
exist that are beyond the scope of the prescriptive requirements of
this
chapter.
The provisions of this chapter do not apply to structures, or portions
thereof, constructed on a concrete slab on grade.
The details and prescriptive provisions herein are
not intended to be
the only acceptable strengthening methods permitted. Alternate details
and methods may be used when approved by the building official.
Approval
of alternates shall be based on test data showing that the method or
material
used is at least equivalent in terms of strength, deflection and
capacity
as provided by the prescriptive methods and materials. See Table A-6-C
for the capacities provided by the prescriptive elements and
connections.
The provisions of this chapter may be used to
strengthen historic structures
provided they are not in conflict with other related provisions and
requirements
that may apply.
A601.3 Alternative Design Procedures. When
analysis by an engineer or
architect is required in accordance with Section A601.2, such analysis
shall be in accordance with all requirementsof the Building Code,
except
that the base shear may be determined in accordance with the
following:
V = 0.33ZW (A1-1)
SECTION A602 - DEFINITIONS
For the purpose of this chapter, in addition to
the applicable definitions
in the Building Code, certain additional terms are defined as follows:
CHEMICAL ANCHOR is an assembly consisting of a
threaded rod, washer,
nut and chemical adhesive approved by the building official for
installation
in existing concrete or masonry.
COMPOSITE PANEL is a wood structural panel product
composed of a combination
of wood veneer and wood-based material and bonded with waterproof
adhesive.
CRIPPLE WALL is a wood-framed stud wall extending
from the top of the
foundation to the underside of the lowest floor framing.
EXPANSION BOLT is a single assembly approved by
the building official
for installation in existing concrete or masonry.For the purpose of
this
chapter, expansion bolts shall contain a base designed to expand when
properly
set, wedging the bolt in the predrilled hole. Assembly shall also
include
appropriate washer and nut.
ORIENTED STRAND BOARD (OSB) is a mat-formed wood
structural panel product
composed of thin rectangular wood strands or wafers arranged in
oriented
layers.
PERIMETER FOUNDATION is a foundation system that
is located under the
exterior walls of a building.
PLYWOOD is a wood structural panel product
composed of sheets of wood
veneer bonded together with the grain of adjacent layers oriented at
right
angles to one another.
SNUG-TIGHT is as tight as an individual can torque
a nut on a bolt by
hand using a wrench with a 10-inch (254 mm) long handle and the point
at
which the full surface of the plate washer is contacting the wood
member
and slightly indents the wood surface.
WAFERBOARD is a mat-formed wood structural panel
product composed of
thin rectangular wood wafers arranged in random layers and bonded with
waterproof adhesive.
WOOD STRUCTURAL PANEL is a structural panel
product composed primarily
of wood and meeting the requirements of United States Voluntary Product
Standard PS 1 and United States Voluntary Product Standard PS 2. Wood
structural
panels include all-veneer plywood, composite panels containing a
combination
of veneer and wood-based material, and mat-formed panels such as
oriented
strand board and waferboard.
SECTION A603 - STRUCTURAL WEAKNESSES
For the purpose of this chapter, structural
weaknesses shall be as specified
below.
1. Sill plates or floor framing that are supported
directly on the ground
without an approved foundation system.
2. A perimeter foundation system that is
constructed only of wood posts
supported on isolated pad footings.
3. Perimeter foundation systems that are not
continuous.
EXCEPTIONS: 1. Existing single-story exterior
walls not exceeding 10
feet (3048 mm) in length forming an extension of floor area beyond the
line of an existing continuous perimeter foundation.
2. Porches, storage rooms and similar spaces not
containing fuel- burning
appliances.
4. A perimeter foundation system that is constructed of unreinforced
masonry.
5. Sill plates that are not connected to the
foundation or are connected
with less than what is required by the Building Code.
EXCEPTION: When approved by the building official,
connections of a
sill plate to the foundation made with other than sill bolts may be
accepted
if the capacity of the connection is equivalent to that required by the
Building Code.
6. Cripple walls that are not braced in accordance with the
requirements
of Section A604.4 and Table A-6-A or cripple walls not braced with
diagonal
sheathing or wood structural panels in accordance with the Building
Code.
SECTION A604 - STRENGTHENING REQUIREMENTS
A604.1 General.
A604.1.1 Scope. The structural weaknesses noted in
Section A603 shall
be strengthened in accordance with the requirements of this section.
Strengthening
work may include both new construction and alteration of existing
construction.
Except as provided herein, all strengthening work and materials shall
comply
with the applicable provisions of the Building Code. Alternate methods
of strengthening may be used provided such systems are designed by an
engineer
or architect and approved by the building official.
A604.1.2 Condition of existing wood materials. All
existing wood materials
that will be a part of the strengthening work (sills, studs, sheathing,
etc.) shall be in a sound condition and free from defects that
substantially
reduce the capacity of the member. Any wood material found to contain
fungus
infection shall be removed and replaced with new material. Any wood
material
found to be infested with insects or to have been infested with insects
shall be strengthened or replaced with new materials to provide a net
dimension
of sound wood at least equal to its undamaged original dimension.
A604.1.3 Floor joists not parallel to foundations.
Floor joists framed
perpendicular or at an angle to perimeter foundations shall be
restrained
by either an existing nominal 2-inch (51 mm) wide continuous rim joist
or by nominal 2-inch (51 mm) wide full depth blocking between alternate
joists in one- and two-story buildings, and between each joist in
three-story
buildings. Existing blocking for multistory buildings must occur at
each
joist space above a braced cripple wall panel.
Existing connections at the top and bottom edge of
an existing rim joist
or blocking need not be verified in one-story buildings. In multistory
buildings the existing top edge connection need not be verified;
however,
bottom edge connection to either the foundation sill plate or top plate
of a cripple wall shall be verified. The minimum existing bottom edge
connection
shall consist of 8d toe nails spaced 6 inches (152 mm) apart for a
continuous
rim joist or three 8d toenails per block. When this minimum bottom edge
connection is not present, or cannot be verified, a supplemental
connection
installed as shown in Figure A-6-8 shall be provided.
Where an existing continuous rim joist or the
minimum existing blocking
does not occur, new 3/4-inch (19 mm) wood structural panel blocking
installed
tightly between floor joists and nailed as shown in Figure A-6-8 shall
be provided at the inside face of the cripple wall and nailed as shown
in Figure A-6-8. In lieu of 3/4-inch (19 mm) wood structural panel
blocking,
tightfitting, full depth 2 (51 mm) blocking, may be used. New
blocking
may be omitted where it will interfere with vents or plumbing that
penetrates
the wall.
A604.1.4 Floor joists parallel to foundations.
Where existing floor
joists are parallel to the perimeter foundations, the end joist shall
be
located over the foundation and, except for required ventilation
openings,
shall be continuous and in continuous contact with the foundation sill
plate or top plate of the cripple wall. Existing connections at the top
and bottom edge of the end joist need not be verified in one-story
buildings.
In multistory buildings, the existing top edge connection of the end
joist
need not be verified; however, the bottom edge connection to either the
foundation sill plate or the top plate of a cripple wall shall be
verified.
The minimum bottom edge connection shall be 8d toenails spaced 6 inches
(152 mm) apart. If this minimum bottom edge connection is not present,
or cannot be verified, a supplemental connection installed as shown in
Figure A-6-9 shall be provided.
A604.2 Foundations.
A604.2.1 New perimeter foundations. New perimeter
foundations shall
be provided for structures with the structural weaknesses noted in
Items
1 and 2 of Section A603. Soil investigations or geotechnical studies
are
not required for this work unless the building is located in a special
study zone as designated by the jurisdiction or other public agency.
A604.2.2 Foundation evaluation by engineer or
architect. Partial perimeter
foundations or unreinforced masonry foundations shall be evaluated by
an
engineer or architect for the force levels noted in Formula (A1-1).
Test
reports or other substantiating data to determine existing foundation
material
strengths shall be submitted for review. When approved by the building
official, these foundation systems may be strengthened in accordance
with
the recommendations included with the evaluation in lieu of being
replaced.
EXCEPTION: In lieu of testing existing foundations
to determine material
strengths and when approved by the building official, a new
nonperimeter
foundation system, designed for the forces noted in Formula (A1-1), may
be used to resist all exterior wall lateral forces.
A604.2.3 Details for new perimeter foundations. All new perimeter
foundations
shall be continuous and constructed according to one of the details
shown
in Figure A-6-1 or A-6-2.
EXCEPTIONS: 1. When approved by the building
official, the existing
clearance between existing floor joists or girders and existing grade
below
the floor need not comply with the Building Code.
2. When approved by the building official, and
when designed by an engineer
or architect, partial perimeter foundations may be used in lieu of a
continuous
perimeter foundation.
A604.2.4 Required compressive strength. New concrete foundations shall
have a minimum compressive strength of 2,500 psi (17.24 MPa) at 28
days.
A604.2.5 New hollow-unit masonry foundations. New
hollowunit masonry
foundations shall be solidly grouted. Mortar shall be Type M or S, and
the grout and masonry units shall comply with the Building Code.
A604.2.6 Reinforcing steel. Reinforcing steel
shall comply with the
requirements of the Building Code.
A604.3 Foundation Sill Plate Anchorage.
A604.3.1 Existing perimeter foundations. When the
building has an existing
continuous perimeter foundation, all perimeter wall sill plates shall
be
bolted to the foundation with chemical anchors or expansion bolts in
accordance
with Table A-6-A.
Anchors or bolts shall be installed in accordance
with Figure A-6-3
with the plate washer installed between the nut and the sill plate. The
nut shall be tightened to a snug-tight condition after curing is
complete
for chemical anchors and after expansion wedge engagement for expansion
bolts. The installation of nuts on all bolts shall be subject to
verification
by the building official.
Where existing conditions prevent anchor or bolt
installation through
the sill plate, this connection may be made in accordance with Figure
A-6-4A,
A-6-4B or A-6-4C. The spacing of these alternate connections shall
comply
with the maximum spacing requirements of Table A-6-A. Expansion bolts
shall
not be used when the installation causes surface cracking of the
foundation
wall at the location of the bolt.
A604.3.2 Placement of chemical anchors and
expansion bolts. Chemical
anchors or expansion bolts shall be placed within 12 inches (305 mm),
but
not less than 9 inches (229 mm), from the ends of sill plates and shall
be placed in the center of the stud space closest to the required
spacing.
New sill plates may be installed in pieces when necessary because of
existing
conditions.For lengths of sill plate greater than 12 feet (3658 mm),
anchors
or bolts shall be spaced along the sill plate as noted in Table
A-6-A.For
other lengths of sill plate, see Table A-6-B. For lengths of sill
plates
less than 30 inches (762 mm), a minimum of one anchor or bolt shall be
installed.
EXCEPTION: Where physical obstructions such as
fireplaces, plumbing
or heating ducts interfere with the placement of an anchor or bolt, the
anchor or bolt shall be placed as close to the obstruction as possible,
but not less than 9 inches (229 mm)from the end of the
plate.Center-to-center
spacing of the anchors or bolts shall be reduced as necessary to
provide
the minimum total number of anchors required based on the full length
of
the wall. Center-to-center spacing shall not be less than 12 inches
(305
mm).
A604.3.3 New perimeter foundations. Sill plates for new perimeter
foundations
shall be bolted as required by Table A-6-A and as shown in Figure A-6-1
or A-6-2.
A604.4 Cripple Wall Bracing.
A604.4.1 General. Exterior cripple walls, not
exceeding 4 feet (1219
mm) in height, shall use the prescriptive bracing method listed below.
Cripple walls over 4 feet (1219 mm) in height require analysis by an
engineer
or architect in accordance with Section A601.3.
A604.4.1.1 Sheathing installation requirements.
Wood structural panel
sheathing shall not be less than 15/32-inch (12 mm) thick and installed
in accordance with either Figure A-6-5 or A-6-6. All individual pieces
of wood structural panels shall be nailed with 8d common nails spaced 4
inches (102 mm) on center at all edges and at 12 inches (305 mm) on
center
at each intermediate support with not less than two nails for each
stud.
Nails shall be driven so that their heads on crowns are flush with the
surface of the sheathing and shall penetrate the supporting member a
minimum
of 11/2 inches (38 mm). When a nail fractures the surface, it shall be
left in place and not counted as part of the required nailing. A
new 8d nail shall be located within 2 inches (51 mm) of the discounted
nail and hand driven flush with the sheathing surface. All horizontal
joints
must occur over nominal 2-inch-by-4-inch (51 mm by 102 mm) blocking
installed
with the nominal 4-inch (102 mm) dimension against the face of the
plywood.
Vertical joints at adjoining pieces of wood structural panels shall be
centered on existing studs such that there is a minimum 1/8 inch (3.2
mm)
between the panels and the nails are placed a minimum of 1/2 inch (12.7
mm) from the edges of the existing stud. Where such edge distances
cannot
be maintained because of the width of the existing stud, a new stud
shall
be added adjacent to the existing studs and connected in accordance
with
Figure A-6-7.
604.4.2 Distribution and amount of bracing. See
Table A-6-A and Figure
A-6-10 for the distribution and amount of bracing required. Each braced
panel must be at least two times the height of the cripple stud wall
but
not less than 48 inches (1219 mm) in length or width. Where the minimum
amount of bracing prescribed in Table A-6-A cannot be installed along
any
walls, the bracing must be designed in accordance with Section A601.3.
EXCEPTION: Where physical obstructions such as
fireplaces, plumbing
or heating ducts interfere with the placement of cripple wall bracing,
the bracing shall then be placed as close to the obstruction as
possible.
Total amount of bracing required shall not be reduced because of
obstructions.
A604.4.3 Stud space ventilation. When bracing materials are installed
on the interior face of studs forming an enclosed space between the new
bracing and existing exterior finish, each braced stud space must be
ventilated.
Adequate ventilation and access for future inspection shall be provided
by drilling one 2-inch to 3-inch (51 mm to 76 mm) diameter round hole
through
the sheathing nearly centered between each stud at the top and bottom
of
the cripple wall. Such holes should be spaced a minimum of 1-inch (25
mm)
clear from the sill or top plates. In stud spaces containing sill
bolts,
the hole shall be located on the center line of the sill bolt but not
closer
than 1-inch (25 mm) clear from the nailing edge of the sheathing. When
existing blocking occurs within the stud space, additional ventilation
holes shall be placed above and below the blocking or the existing
block
shall be removed and a new nominal 2-inch by 4-inch (51 mm by 102 mm)
block
installed with the nominal 4-inch (102 mm) dimension against the face
of
the plywood. For stud heights less than 18 inches (457 mm), only one
ventilation
hole will be provided.
A604.4.4 Existing underfloor ventilation. Existing
underfloor ventilation
shall not be reduced without providing equivalent new ventilation as
close
to the existing as possible. Braced panels may include underfloor
ventilation
openings when the height of the opening, measured from the top of the
foundation
wall to the top of the opening, does not exceed 25 percent of the
height
of the cripple stud wall; however, the length of the panel shall be
increased
a distance equal to the length of the opening or one stud space
minimum.
Where an opening exceeds 25 percent of the cripple wall height, braced
panels shall not be located where the opening occurs. See Figure
A-6-7.
EXCEPTION: For homes with a post and pier
foundation system where a
new continuous perimeter foundation system is being installed, new
ventilation
shall be provided in accordance with the Building Code.
A604.5 Quality Control. All work shall be subject to inspection by
the building official including, but not limited to:
1. Placement and installation of new chemical
anchors or expansion bolts
installed in existing foundations. Special inspection is not required
for
chemical anchors installed in existing foundations regulated by the
presecriptive
provisions of this chapter.
2. Installation and nailing of new cripple wall
bracing.
3. Any work may be subject to special inspection
when required by the
building official in accordance with the Building Code.
A604.6 Phasing of the Strengthening Work. When
approved by the building
official, the strengthening work contained in this chapter may be
completed
in phases. The strengthening work in any phase shall be performed on
two
parallel sides of the structure at the same time.
|